IP Supervisor (AOR-IP-SUP) Installation

IP Supervisor (AOR-IP-SUP) Installation


Cabling

Power

The AOR-IP-SUP includes a 24vdc 0.5A wall plug power adapter that will need to be connected to a 120v power supply, backup power may be required as per local codes.  

On the X600M TM , the black/white wire connects to V+   and the black wire connects to V- .

Communication

A single CAT5e, or better will be needed to provide communications for the AOR-IP-SUP .  This will connect to the ENET 1 .
The included Expansion cable is used to connect the X600M TM  with the X12S TM , via the Expansion ports.
There are eight normally open relays on the X12S TM  , that will accept 30AWG-14AWG wire, that is rated for at least 75°C.

14-Pin Connector Pinout
Terminal
Description
1NO
Relay 1 NO
2NO
Relay 2 NO
3NO
Relay 3 NO
4NO
Relay 4 NO
1-4COM
Relay 1,2,3,4 COM
1-4COM
Relay 1,2,3,4 COM
1-4COM
Relay 1,2,3,4 COM
5NO
Relay 5 NO
6NO
Relay 6 NO
7NO
Relay 7 NO
8NO
Relay 8 NO
5-8COM
Relay 5,6,7,8 COM
5-8COM
Relay 5,6,7,8 COM
5-8COM
Relay 5,6,7,8 COM

Preparing the Enclosure

To prepare the mounting enclosure, a hole must be drilled to allow the cables to pass through, and the mounting tabs must be installed per the instructions included.
  1. Remove the mounting panel by removing the four(4) 9/16" nuts at the corners of the panel.
  2. Drill a hole large enough for an RJ-45 Ethernet connector, and the power cord to pass through.
  3. Following the instructions that were included by the manufacturer, attach the four (4) Mounting tabs.

Mounting the Enclosure

Mount the enclosure to the wall using fasteners and anchors appropriate for the construction of the wall.

Finish the installation by connection the Ethernet cable and power cable as outlined in the Cabling section above.







    • Related Articles

    • AOR-IP Supervisor Configuration

      The AOR-IP-SUP comes pre-configured, for standard subnet used in the AOR-IP-SUP, but will need the proper configuration loaded and the scripts modified for the number of stations, in order to monitor the correct Network Devices. Configuration ...
    • AOR-IP Command Unit Installation

      This document covers the physical installation of the following AOR-IP Command Unit models: AOR-IP-40-CU AOR-IP-80-CU AOR-IP-120-CU AOR-IP-160-CU Fasteners The AOR-IP Command units can be surface mounted or flush mounted, as the particular ...
    • AOR-IP Auxiliary Command Unit (ACU) Installation

      This document covers the physical installation of the following AOR-IP Auxiliary Command Unit models: AOR-IP-40-ACU AOR-IP-80-ACU AOR-IP-120-ACU AOR-IP-160-ACU Fasteners  The AOR-IP Command units can be surface mounted or flush mounted, as the ...
    • Area of Rescue Command Unit Installation Guide for Model AOR-8 and Model AOR-16

      Important Notice THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED CE PRODUIT DOIT ÊTRE INSTALLÉ SELON LE CODE ...
    • AOR-IP Command Unit (CU) Configuration

      This document covers the basic configuration needed for any of the AOR-IP Command units. (AOR-IP-40-CU, AOR-IP-80-CU, AOR-IP-120-CU, AOR-IP-160-CU) General Information The AOR-IP command units ship pre-configured for up to 160 call station, one ...